Condensing heat recovery · CXL / DXL

FlueBank: 8.4–8.5% less fuel from the heat your boiler throws away

A condensing heat-recovery unit installed in the flue of an industrial steam boiler, downstream of the existing feedwater economizer. It cools flue gas from about 187 °C to 50 °C, preheats make-up water and then feedwater, and the saving is proved with IPMVP Option B measurement — not estimated.

Short answer: FlueBank is a flue-gas condensing economizer in two configurations — CXL (single stage, round duct) and DXL (two stage, two-flue). Measured on LPG it recovers 77 kW per tonne per hour of steam and cuts fuel energy by 8.4–8.5% at ±1.0% uncertainty. It works on natural gas, LPG and CNG; on 0.01% S diesel oil it condenses to 45 °C with an AL-6XN bundle; on biomass it runs non-condensing at 80 °C.

8.4–8.5%fuel energy saved, measured (IPMVP Option B, ±1.0%)
187 → 50 °Cflue gas in and out on gas fuels
77 kWrecovered per t/h of steam, any boiler size
0 capexESCO model: we own the unit, owner takes 30%
Download the three M&V reports See the live measurement dashboard

Which configuration fits which stack

CXL is the single-stage unit for a round flue: one condensing section, one condensate drain, the shortest installation. DXL is the two-stage unit for a rectangular or two-flue stack: a first sensible stage and a second condensing stage, with the bypass between them. Model codes are assigned per 100 kW of recovered duty (78.8 kW per t/h of steam), so a 10 t/h boiler is VX-CXL-08xx and a 6 t/h boiler is VX-DXL-05xx; above the standard frame the unit is split into modules.

ItemCXLDXL
StagesSingle-stage condensingTwo-stage, sensible then condensing
StackRound ductRectangular or two-flue
Flue gas flowup to 250,000 lb/hr; modules above
Tube bundleSS 316L standard; AL-6XN (UNS N08367) for sulphur or chloride duty
Bypassinternal diverter + actuator, driven by steam pressure (delivered as standard)
Condensatedrain with trap, neutralisation for acid condensate
Measured case10 t/h (Avis) and 20 t/h (Boiler house No.1)6 t/h (Northline)

Fuel-by-fuel limits — why the same unit saves different amounts

The cold end of the exchanger is set by the dew point of the flue gas, so the fuel decides how deep the unit can go and whether latent heat is recovered at all. This is the single most useful table when comparing a gas project with an oil or biomass project.

FuelCold endLatent heatMeasured or engineering resultMaterial
Natural gas, CNG, LPG50 °CYes8.4–8.5% fuel saving (measured on LPG)SS 316L
Diesel oil 0.01% S45 °CYes, small share5.9–6.8% (engineering case, 2026-11)AL-6XN
Biomass, wood chips 30% moisture80 °CNo4.9–5.7% (engineering case, non-condensing)316L not sufficient for chlorides

Measured = LPG reference installations with 12-month baseline and interval data. Engineering cases use the same boiler, the same steam duty and the same measurement method, with the fuel-specific cold-end limit and measured fuel price; they are labelled as cases, not as verified installations.

Three boilers, measured

ProjectSteamRecoveredFuel savingSaving per year (LPG)
Boiler house No.1 — CXL20,000 kg/h1,548 kW8.47%USD 1,128,262
Avis Foods — CXL10,000 kg/h767 kW8.40%USD 559,043
Northline Foods — DXL6,000 kg/h464 kW8.46%USD 338,049

8,000 operating hours per year, LPG at USD 26.70 per MMBtu (HHV 49.6 MJ/kg, VND 33,000/kg at 26,300 VND/USD), full load. Full reports: /vx/pulse/reports/.

How the saving is proved

The unit is sold with the measurement, not after it. IPMVP Option B — retrofit isolation with all parameter measurement — means every term of the saving equation is metered: fuel mass flow, steam flow, feedwater flow and temperature, flue gas temperature in and out, oxygen and ambient conditions, at 15-minute intervals, with a calibrated tag register and a stated uncertainty of ±1.0%. Savings are baseline corrected to reporting conditions minus the measured reporting period, never the difference of two estimates.

The same data feeds the live dashboard, so the owner and the bank see the same number, and the ESCO share is calculated from the metered saving — 70% to Vegax, 30% to the plant owner, on the whole verified saving against baseline, for five years, then the unit transfers and the owner keeps 100%.

Questions buyers ask before a site visit

How much fuel can a condensing economizer save on a 10 t/h boiler?

8.4–8.5% of fuel energy on gas fuels, which is 767 kW recovered on a 10 t/h boiler. In money that is about USD 559,000 per year on LPG at USD 26.70/MMBtu and 8,000 hours.

Will it work on our diesel oil or biomass boiler?

Yes, with a different cold-end limit. On 0.01% S diesel the bundle must be AL-6XN and the flue goes to 45 °C (5.9–6.8% saving). On biomass the unit stays non-condensing at 80 °C (4.9–5.7%) and chlorides rule out a standard 316L bundle.

What is the corrosion risk and how is it handled?

Dilute sulphuric condensate forms below the acid dew point. AL-6XN resists pitting where 316L would not; the package includes a condensate drain with neutralisation, a soot blower, and corrosion coupons checked on the service interval. These are in the delivered scope and in the contract, not left to the operator.

What happens when the boiler runs at low load?

The bypass diverter closes the recovery path and keeps the flue above its dew point, so the cold end is never wet at low load. The bypass is part of the unit.

Does it disturb the boiler draught or the burner?

The unit is sized for the existing flue gas flow with a design pressure drop agreed before the order, and the bypass gives a low-loss path if the boiler must run without recovery. No burner or combustion-control change is part of the scope.

Who maintains it, and what does the owner pay?

Vegax maintains the unit during the five-year term out of its 70% share; the measurement fee is inside that share. The owner pays nothing up front and nothing per month.

Can we buy the unit outright instead?

Yes. The unit is priced by recovered kW, and an outright purchase removes the sharing model; the measurement service can still be contracted separately.

What do you need to quote a project?

Flue gas flow, flue temperature and oxygen at full and minimum load, fuel type and its price, steam pressure and flow, feedwater and make-up water temperatures, stack dimensions and a sketch of the flue run. With those six items a firm duty and a saving figure can be produced in a week.

Read the M&V reports Send project data

Technical guides

Short, sourced answers to the questions buyers ask before a site visit:

GuideWhat it answers
How much can it saveMeasured kW and dollars by boiler size
Condensing vs conventional economizerWhat the extra stage buys
Fuel limits and dew pointsWhy LPG, diesel and biomass differ
0.01% S diesel oil45 °C cold end with AL-6XN
BiomassWhy the cold end stops at 80 °C
IPMVP Option BHow the saving is proved
Cost and paybackCapital and months to payback
No-capital ESCO modelWho owns what, and when it transfers