Short answer: a conventional economizer cools flue gas to about 150–180 °C and recovers only sensible heat, typically 3–5% of fuel. A condensing economizer cools to 45–50 °C, crosses the water dew point, and recovers latent heat as well — 8.4–8.5% of fuel on gas fuels, measured.
Both devices are heat exchangers in the flue. The difference is the outlet temperature, and the outlet temperature decides whether the water vapour in the flue gas condenses. At 180 °C nothing condenses and only sensible heat is recovered. At 50 °C most of the water vapour has condensed and its latent heat — roughly 2.4 MJ per kg of water — is added to the recovered duty.
That is why the condensing unit recovers about twice the energy of a conventional economizer from the same flue gas flow, and why the extra gain is not available at all on a fuel whose flue gas cannot be taken below its dew point.
Both columns are for a 10 t/h LPG boiler at 8,000 hours per year. The conventional case is a typical feedwater economizer at 160 °C outlet; the condensing case is measured.
| Conventional economizer | Condensing (FlueBank) | |
|---|---|---|
| Flue gas outlet | 150–180 °C | 50 °C (45 °C on diesel, AL-6XN) |
| Latent heat | Not recovered | Recovered |
| Fuel saving on gas | 3–5% | 8.4–8.5% measured |
| Recovered duty, 10 t/h | about 350 kW | 767 kW |
| Drain / neutralisation | None | Required |
| Cold-end material | Carbon steel / 316L | 316L or AL-6XN by fuel |
Conventional column is a typical design range; condensing column is measured on LPG reference installations.
A drain: condensate forms at 45–50 °C and must leave the unit, neutralised when the fuel contains sulphur.
A bypass with an actuator, so the cold end stays above the dew point when the boiler load is too low to use the recovered heat.
Material choice set by the fuel: SS 316L on clean gas, AL-6XN where sulphuric or chloride condensate forms.
Measurement: a condensing unit is normally sold against a saving figure, so it needs the tags, the logger and the uncertainty statement that make the figure provable.
On dirty fuels and on boilers with no cold sink. If the only available sink is feedwater at 90 °C, the cold end cannot go to 50 °C and the condensing gain disappears — then a conventional economizer or an air preheater is the correct choice. A fuel with chlorides or heavy fouling also argues against a wet cold end.