How much can a condensing economizer save on a steam boiler?

Measured answer: on natural gas, LPG or CNG a condensing economizer saves 8.4–8.5% of boiler fuel energy, which is 77 kW recovered per tonne per hour of steam — 464 kW on a 6 t/h boiler, 767 kW on 10 t/h, 1,548 kW on 20 t/h. On 0.01% S diesel oil the saving is 5.9–6.8%; on biomass 4.9–5.7%.

Why the saving is a percentage of fuel, not a fixed number

A condensing economizer recovers heat that the boiler already paid for and sent up the stack. The recovered duty scales with flue gas mass flow, so it scales with steam output: the same machine family delivers the same percentage on a 6 t/h boiler as on a 20 t/h one. That is why the honest way to quote it is a percentage of fuel plus a kW figure per tonne of steam.

The flue gas leaves the boiler at about 187 °C and is cooled to 50 °C on gas fuels. Two heat flows are recovered: sensible heat as the gas cools, and latent heat as the water vapour in the products of combustion condenses.

Measured values, three boilers

The three reference installations below were measured under IPMVP Option B with a 12-month baseline, 15-minute interval data and a stated uncertainty of ±1.0%, at 8,000 operating hours per year.

ProjectSteamRecoveredFuel savingSaving / year (LPG)
Boiler house No.1 — CXL20,000 kg/h1,548 kW8.47%USD 1,128,262
Avis Foods — CXL10,000 kg/h767 kW8.40%USD 559,043
Northline Foods — DXL6,000 kg/h464 kW8.46%USD 338,049

Measured, IPMVP Option B, ±1.0%, 8,000 h/year, LPG at USD 26.70/MMBtu.

What it means in money

Fuel price does more work than the percentage. On LPG at USD 26.70 per MMBtu the 10 t/h boiler saves USD 559,043 a year; the same heat recovery on a cheaper fuel saves proportionally less money even though the percentage is identical. The reverse is true for diesel oil: fewer percentage points, more money per point, because the fuel costs more per MMBtu.

What limits the saving

The cold end of the exchanger. Water vapour in the flue gas condenses only below its dew point — 54.6 °C for LPG, about 47 °C for 0.01% S diesel, around 55–60 °C for biomass. Below that, acid dew point and chloride limits decide how deep the unit may go, which is why the same recovery unit reports different percentages on different fuels.

Related

Download the M&V reports Send project data
Vegax Energy · NCK Group LLC · FlueBank condensing heat recovery (CXL / DXL) · Measurement: IPMVP Option B, ±1.0% · product page · M&V reports