Type the numbers from the boiler room. The tool balances the flue gas against the water side the way a real audit does — and tells you which of the two is the limit. Same arithmetic that reproduced Cain's own published studies within 4 %.
Excess air is derived from O₂: EA = O₂ / (20.9 − O₂). Everything is computed in the browser; nothing you type leaves the page.
Screening calculation, not a quotation. Final sizing needs a stack traverse, a fuel analysis and the boiler's load profile — that is the site survey, and it is what the paid audit adds.
The report carries every input, every intermediate number and the condensing verdict, so a colleague can check it. Enter a work email and we open the finished report — nothing is charged, and no account is needed.
| Gas side | Flue mass = (burner input ÷ fuel heating value) × stoichiometric air/fuel × (1 + EA); then q = ṁ × cp × (Tin − Tout), with cp = 0.27 BTU/lb·°F. |
|---|---|
| Water side | q = 500 × GPM × ΔT. This is the hard limit: if the sink cannot absorb the heat, the economizer cannot recover it, whatever the flue gas offers. |
| Recovered | The smaller of the two. The tool prints which side is limiting on purpose — that single line decides whether you need a bigger coil or a colder sink. |
| Money | Recovered heat ÷ boiler efficiency = fuel not bought, because every BTU recovered in the feedwater displaces 1/η BTU at the burner. We print η next to it; a heat-credit calculation without η overstates the saving by 25 % at η = 0.80. |
| Dew point | Computed from the water vapour in the flue gas. Below it the condensing stage works and latent heat is available; above it you are only moving heat above the water dew point. |
Verified against Cain's own published savings studies: water side within 4 %, gas side within 3 % on identical inputs.