A saving you cannot measure is a saving you cannot invoice, defend or repeat. VX-MV is the metering package that turns the flue, the fuel and the condensate into numbers a third party can re-derive.
The instrument list is fixed per site at survey. Nothing enters the saving calculation unless it is on this list, and every channel is time-stamped at the gateway — not in the dashboard.
| Stream | Instrument | Range / signal | Why it is there |
|---|---|---|---|
| Fuel | Mass flow meter on the fuel line | 4–20 mA, ±0.5 % of reading | The number the gas invoice is calculated from |
| Steam | Flow meter, cross-checked against feedwater | Pulse / 4–20 mA | Normalises the saving per tonne of steam, not per hour |
| Flue gas temperature | Type K thermocouples, in and out of the economizer | 0–600 °C | Independent check on the heat recovered |
| Flue gas O₂ | In-situ O₂ analyser (Autoflame EGA where an Mk8 is fitted) | 0–21 % O₂ | Separates combustion loss from recovery gain |
| Condensate | Flow meter on the economizer drain | 0–1,000 kg/h | Water recovered, and the latent share of the gain |
| Combustion trim | VX-CT — O₂ trim on the burner controller, correcting damper and air-fuel position | O₂ 0–21 %, held at 2.3–3.0 % | Keeps the flue O₂ at target, so excess air is what shrinks — not something the economizer has to compensate for |
X-Device-Key. No inbound port is opened at the plant.We do not hide the bill of materials — a customer should know what is bolted to their boiler house:
| Field I/O | Moxa ioLogik remote I/O modules on the analogue and pulse points (fuel, steam, flue, water). Modbus into the edge computer, so a point can be re-ranged without touching a wire. |
|---|---|
| Edge computer | Moxa UC-4400A — Arm Cortex-A53 quad-core, LTE/5G and Wi-Fi 6E on the cellular models, TPM 2.0, CAN and serial for meters that speak neither Ethernet nor Modbus TCP. |
| Link | Outbound-only from the plant to the PULSE endpoint. No inbound port is opened at the boiler house, and no control write path exists from the cloud to the burner. |
| Cloud | PULSE — the same application that serves the public reference plants: per-minute readings, hourly and daily statistics, the M&V report. |
Sources: Moxa UC-4400A series. What we do not publish is how the points are scaled, cross-checked against each other and reconciled into a verified saving — that is the integration work, and it is what a customer pays for.
Current issues of the documents this module is built on. Files we are licensed to pass on are served here; the rest we send on request under the manufacturer's own terms.